SEW Eurodrive · MOVIDRIVE system
The signal level from Encoder 2 is excessively high, exceeding the permitted limit during monitoring. This often points to an incorrect gear ratio configured for the resolver or a wiring issue, potentially leading to inaccurate position readings.
Click steps to track your progress.
Verify drive parameter P3-62 (Resolver transformation ratio) matches the datasheet specifications for Encoder 2.
Measure the differential voltage of the Encoder 2 signals (e.g., Sin+ to Sin-, Cos+ to Cos-) at drive terminal X2 using an oscilloscope, observing peak-to-peak amplitude.
Power down the drive, disconnect Encoder 2 cable, and measure resistance between each signal line (e.g., Sin+, Sin-) and the supply voltage (+10V) at the encoder connector.
Test the drive's Encoder 2 input with a known-good, correctly configured encoder to isolate the issue to the encoder or drive.