SEW Eurodrive · MOVIDRIVE system
The current load on the 24 V standby supply voltage in the MOVIDRIVE® system is too high. This overcurrent causes the device's internal signal output to de-energize. Leaving this unresolved can lead to system instability, unexpected shutdowns, and potential damage to internal components from sustained overload.
Click steps to track your progress.
Disconnect all external loads from the 24VDC output terminals (e.g., X10/X11) and measure the current draw from each device individually.
Measure the voltage at the 24VDC output terminals (e.g., X10/X11) with a multimeter to verify it is stable and within tolerance.
With all external loads disconnected, measure the current flowing from the 24VDC output using an ammeter to check for internal drive leakage.
Isolate sections of the 24VDC external wiring by disconnecting them segment by segment and re-applying power to identify short circuits or ground faults.
Refer to the drive manual to verify the maximum permissible 24VDC output current and ensure connected loads are within limits.