Siemens · SINAMICS S120/S150 Reference List
This alarm is initiated when the actual temperature (r4105[2]) for channel 2 on Terminal Module 120 (TM120) or Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[4]). A timer (p4103[2]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[2]).
Click steps to track your progress.
Measure the actual temperature of the component associated with channel 2 using a calibrated handheld device and compare it to r4105[2].
Ensure all air inlets and outlets for the control cabinet and the TM120/TM150 module are clear and free of obstructions.
Examine the operational data for the equipment on channel 2 for any trends indicating increasing power consumption or operational stress.
Check that parameter p4102[4] (Alarm threshold channel 2) is set at a level that provides an adequate early warning without nuisance tripping.
Implement a regular monitoring schedule for r4105[2] to track temperature behavior and identify any accelerating temperature rises.