This alarm is initiated when the actual temperature (r4105[4]) for channel 4 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[8]). A timer (p4103[4]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[4]).
Click steps to track your progress.
1. Read the actual temperature r4105[4] in the drive diagnostics and compare it with the component's specified maximum continuous operating temperature.
2. Verify the configured alarm threshold p4102[8] and the timer delay p4103[4] to ensure they are appropriate for the application.
3. Inspect the cooling system of the monitored component for obstructions, fan functionality, or proper heat dissipation.
4. Measure the resistance of the temperature sensor connected to TM150 channel 4 and compare it to its nominal value (e.g., 100 Ohms for Pt100 at 0°C).
5. Clean the component's cooling fins and ensure free airflow around the motor or equipment, if applicable.