Siemens · SINAMICS S120/S150 Reference List
This alarm is initiated when the actual temperature (r4105[8]) for channel 8 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[16]). A timer (p4103[8]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[8]).
Click steps to track your progress.
1. Read the current temperature r4105[8] from the drive and evaluate its trend over time for unusual patterns.
2. Confirm that the alarm threshold p4102[16] and the timer delay p4103[8] are correctly parameterized for the application.
3. Inspect the general cooling conditions of the area surrounding the component connected to channel 8, checking for proper ventilation.
4. Disconnect the sensor from TM150 channel 8 and perform a continuity and resistance test on the sensor wiring to the component.
5. Verify the operational status of any associated external cooling fans or liquid cooling systems for the monitored component.