Siemens · SINAMICS S120/S150 Reference List
This alarm is initiated when the actual temperature (r4105[9]) for channel 9 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[18]). A timer (p4103[9]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[9]).
Click steps to track your progress.
1. Check the live temperature value r4105[9] in the diagnostic parameters of the control system.
2. Review and adjust parameter p4102[18] (alarm threshold) and p4103[9] (alarm timer) to match the component's thermal limits and operational requirements.
3. Use a thermal imaging camera to measure the surface temperature of the component connected to channel 9 to corroborate the sensor reading.
4. Verify the integrity of the wiring to TM150 channel 9, ensuring secure connections at terminals X1.19 and X1.20 (typical for channel 9).
5. Investigate for external heat sources or heating element malfunctions that could be affecting the monitored component.