This alarm is initiated when the actual temperature (r4105[10]) for channel 10 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[20]). A timer (p4103[10]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[10]).
Click steps to track your progress.
1. Monitor the real-time temperature value r4105[10] and the status of the alarm timer p4103[10].
2. Adjust the alarm threshold p4102[20] based on the component's safe operating temperature range specified by the manufacturer.
3. Verify the physical contact of the temperature sensor with the component and reapply thermal paste if necessary.
4. Inspect the sensor cable for TM150 channel 10 for proper shielding and grounding to mitigate EMI.
5. Remove any obstructions from the cooling system of the component and ensure proper airflow.