Siemens · SINAMICS S120/S150 Reference List
This alarm is initiated when the actual temperature (r4105[11]) for channel 11 on Terminal Module 150 (TM150) exceeds its configured alarm threshold (p4102[22]). A timer (p4103[11]) is also started. The alarm will clear once the temperature falls below the threshold, factoring in the defined hysteresis (p4118[11]).
Click steps to track your progress.
1. Read the temperature r4105[11] and the timer value p4103[11] via the drive's diagnostic interface.
2. Review and correct the alarm threshold p4102[22] to be consistent with the component's maximum safe operating temperature.
3. Disconnect the temperature sensor and measure its resistance, then compare it against its nominal values (e.g., Pt100/Pt1000 curve).
4. Check the integrity of the sensor cabling, specifically for loose connections at terminals X1.21 and X1.22 (typical for channel 11) on the TM150.
5. Perform a load test on the component to determine if the temperature increase is correlated with operational demands.