F35207

TM120/TM150 Temperature Fault Channel 0

Siemens · SINAMICS S120/S150 Reference List

What does F35207 mean?

This fault is triggered when the actual temperature (r4105[0]) for channel 0 on the Terminal Module 120 (TM120) or Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[1]), or if an associated timer (p4103[0]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.

Common Causes

  • High ambient temperature within the control cabinet or immediate vicinity of the monitored equipment, exceeding the module's rated operating conditions.
  • Excessive load on the component connected to channel 0, causing its operational temperature to exceed safe limits.
  • Faulty temperature sensor connected to channel 0, inaccurately reporting a higher temperature reading for r4105[0].
  • Blocked ventilation openings, dust accumulation on heat sinks, or cooling fan malfunction affecting the TM120/TM150 module or the monitored component.
  • Parameter p4102[1] (Temperature fault threshold channel 0) set too low for the application's normal operating conditions, leading to premature tripping.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Measure the actual temperature of the monitored component using an external thermal imaging camera or calibrated thermometer and compare it with r4105[0].

  2. 2

    Inspect and thoroughly clean all cooling fins, fans, and ventilation openings on the TM120/TM150 module and the equipment connected to channel 0.

  3. 3

    Verify the integrity and connections of the temperature sensor wiring for channel 0 from the sensor to the TM120/TM150 terminal block for looseness or corrosion.

  4. 4

    Review the operational load on the equipment monitored by channel 0 to ensure it is not exceeding its design limits or duty cycle.

  5. 5

    If the actual temperature is confirmed within safe limits but r4105[0] remains high, replace the temperature sensor associated with channel 0.

  6. 6

    If thorough analysis confirms safe operating temperatures are consistently above the current fault setting, increase parameter p4102[1] (Fault threshold channel 0) to an appropriate value, ensuring adequate safety margin.

Browse all codes in this manual (32)
Verified technical data. Last updated: April 2026