This fault is triggered when the actual temperature (r4105[2]) for channel 2 on the Terminal Module 120 (TM120) or Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[5]), or if an associated timer (p4103[2]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.
Click steps to track your progress.
Verify the actual temperature of the component monitored by channel 2 using a calibrated thermal imager or thermocouple, cross-referencing with r4105[2].
Check and ensure proper airflow by cleaning any blocked vents or filters on the TM120/TM150 module and the associated equipment for channel 2.
Perform a continuity check and visual inspection on the temperature sensor cabling for channel 2 to identify any breaks or poor connections.
Evaluate the operational cycle and load profile of the equipment on channel 2 to ascertain if it is being overstressed.
If the component's physical temperature is normal but r4105[2] is elevated, replace the temperature sensor connected to channel 2.
Consider increasing parameter p4102[5] (Fault threshold channel 2) if system analysis confirms the current setting is too low for the component's safe, sustained operation.