Siemens · SINAMICS S120/S150 Reference List
This fault is triggered when the actual temperature (r4105[4]) for channel 4 on the Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[9]), or if an associated timer (p4103[4]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.
Click steps to track your progress.
Measure the actual operating temperature of the component monitored by channel 4 using a calibrated external device and compare it with r4105[4].
Inspect and clean any cooling fans, filters, and heat sinks associated with the TM150 module and the equipment on channel 4.
Verify the integrity and connection of the temperature sensor wiring for channel 4 from the sensor to the TM150 module.
Review the process load and operating cycle of the equipment connected to channel 4 to identify if it is exceeding its thermal capacity.
If the physical temperature is normal but r4105[4] indicates high, replace the temperature sensor connected to TM150 channel 4.
If analysis confirms safe operational temperatures are higher than the threshold, adjust parameter p4102[9] (Fault threshold channel 4) to an appropriate, safer value.