This fault is triggered when the actual temperature (r4105[5]) for channel 5 on the Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[11]), or if an associated timer (p4103[5]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.
Click steps to track your progress.
Use an independent thermal measurement device to check the actual temperature of the component on channel 5, comparing it with r4105[5].
Clean all air vents, filters, and heat exchange surfaces of the TM150 module and the associated equipment on channel 5.
Examine the wiring connections for the temperature sensor on channel 5 for any loose terminals, corrosion, or damage.
Assess the current operational parameters and load conditions to determine if the equipment on channel 5 is being thermally overstressed.
If the actual temperature is within limits but r4105[5] is high, replace the temperature sensor connected to TM150 channel 5.
If justified by operational data, increase parameter p4102[11] (Fault threshold channel 5) to a setting that aligns with the component's safe operating envelope.