This fault is triggered when the actual temperature (r4105[7]) for channel 7 on the Terminal Module 150 (TM150) exceeds its configured fault threshold (p4102[15]), or if an associated timer (p4103[7]) expires. If a BICO interconnection exists, this fault will cause the drive to shut down. The fault will persist until the temperature falls below the threshold (minus hysteresis) and is acknowledged.
Click steps to track your progress.
Measure the current operating temperature of the component monitored by channel 7 using a reliable external temperature sensor, comparing it with r4105[7].
Ensure proper ventilation paths are clear and clean any dust from the heat sinks and fans of the TM150 module and the equipment on channel 7.
Conduct a continuity test and visual inspection of the wiring for the temperature sensor on channel 7 from the sensor to the TM150 input.
Examine the operational data for the component on channel 7 to confirm it is not running in an overload state or with compromised lubrication.
If the actual temperature is within tolerance but r4105[7] is elevated, replace the temperature sensor connected to TM150 channel 7.
Adjust parameter p4102[15] (Fault threshold channel 7) to a higher, safe value if a thorough engineering review supports it, considering component specifications.