Siemens · SINAMICS S120/S150 Reference List
A general fault has been detected at the drive object connected to the DRIVE-CLiQ socket X103. The fault value (r0949) provides information about the specific underlying fault that first occurred for this drive object. This fault requires immediate acknowledgment.
Click steps to track your progress.
Power down the drive, then visually inspect the entire length of the DRIVE-CLiQ cable connected to socket X103 for physical damage, sharp bends, or cuts. Verify cable shielding is intact and properly grounded at both ends.
Power down the drive, then firmly reseat the DRIVE-CLiQ connector at socket X103 on the drive and at the connected component's port. Ensure the latching mechanism is fully engaged.
Measure the 24VDC supply voltage at the power terminals of the component connected via X103 (if applicable) while the system is powered on, ensuring it remains within +/-10% of 24VDC.
Check drive parameters r0940 (Component type) and r0941 (Topology ID) for the component at X103 and compare them with the actual component type and expected topology. Reconfigure p0940 if incorrect.
If the fault persists, replace the DRIVE-CLiQ cable connected to X103 with a known good, identical length cable to rule out cable failure.
If the fault still persists after verifying cable and power, temporarily replace the DRIVE-CLiQ component connected to X103 with a known good, compatible unit to isolate a component hardware fault.