Yaskawa Drive Fault Codes

60 fault codes documented

CE

MEMOBUS/Modbus Communication Error

A communication error has occurred on the MEMOBUS/Modbus network, preventing the drive from exchanging data correctly with a master controller or other devices. This can lead to loss of remote control, monitoring, or coordinated operation.

CPF02

A/D Conversion Error

An error in the Analog-to-Digital (A/D) conversion circuit, which is responsible for converting analog input signals (e.g., speed reference, feedback) into digital values for the drive's control system. This impacts the accuracy or availability of analog inputs, potentially leading to incorrect operation.

CPF03

Control Board Connection Error

An issue with the physical connection between the main control board and another internal drive component or module. This can prevent proper communication and operation of the drive, leading to unpredictable behavior or complete shutdown.

CPF06

EEPROM Memory Data Error

An error detected in the drive's EEPROM (Electrically Erasable Programmable Read-Only Memory), where parameters and operational data are stored. This can indicate data corruption or a faulty memory chip, potentially causing the drive to operate with incorrect settings or fail to store new ones.

CPF07

Terminal Board Connection Error

An error related to the connection of the drive's terminal board, which provides external input/output connections (e.g., digital inputs, analog outputs). This can lead to loss of external control signals or incorrect feedback, causing operational issues.

CPF08

Terminal Board Connection Error

Similar to CPF07, this indicates a connection issue with the drive's terminal board. This could be a specific type of connection error or related to a different terminal board than CPF07, impacting specific external I/O functions.

CPF11

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF12

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF13

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF14

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF15

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF16

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF17

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF18

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF19

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF20

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF21

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF22

Hybrid IC Error

An error detected in a Hybrid Integrated Circuit (IC) within the drive, typically related to power control or signal processing functions. Hybrid ICs are complex components, and a fault here usually indicates internal damage, affecting drive stability or output.

CPF23

Control Board Connection Error

An issue with the physical connection of the main control board, similar to CPF03, implying a critical link between central processing and other drive sections is compromised. This impacts the overall drive functionality and can lead to operational failures.

CPF24

Drive Unit Signal Fault

A general fault indicating an issue with an internal signal within the drive unit, possibly related to data integrity or synchronization between different drive sub-systems. This points to an internal electronic malfunction affecting reliable operation.

CPF25

Terminal Board Not Connected

The drive has detected that a required terminal board is not physically connected or properly recognized. This prevents the use of external control and feedback signals, making external control of the drive impossible.

CPF26

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF27

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF28

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF29

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF30

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and potential hardware replacement, affecting the drive's core functionality.

CPF33

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF34

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF35

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF36

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF37

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF38

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF39

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF40

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF41

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF42

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

CPF43

Control Circuit Error

A control circuit error indicating a malfunction within the drive's internal control logic or hardware. This fault often points to damaged internal components that necessitate power cycling and replacement of the affected hardware.

E5SI-T3

Watchdog Timer Error

A Watchdog Timer Error indicates that the drive's internal processor has stopped responding or is executing an endless loop. This is a critical software or hardware fault preventing safe operation and indicates damaged hardware requiring power cycling and replacement to restore functionality.

EF0

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF1

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF2

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF3

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF4

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF5

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF6

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF7

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

EF8

External Fault

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

bAT

Digital Operator Battery Voltage Low

The battery voltage within the digital operator (keypad) is critically low, impacting its ability to retain settings or operate correctly when disconnected from the drive. This indicates a potential data loss risk for parameters or logged data.

bUS

Option Communication Error

An error occurred during communication with an installed option card (e.g., network card, encoder card). This indicates a problem with the data exchange between the main drive unit and the option module, which can disrupt control or feedback functions.

boL

Braking Transistor Overload Fault

The internal or external braking transistor has experienced an overload condition, likely due to excessive regenerative energy being dissipated, exceeding its thermal or current limits. This can lead to damage to the transistor, braking resistor, or even the drive itself.

oFA01

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA02

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA03

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA04

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA05

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA06

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA07

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA08

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA09

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.

oFA10

Option Card Fault

An option card fault, indicating a general issue with one of the installed option cards. This requires corrective actions ranging from parameter adjustment to hardware checks or replacement to restore functionality of the option.