Danfoss VLT HVAC

142 fault codes documented

0

Internal fault (Serial port cannot be initialized)

The serial port cannot be initialized. This is an internal software or hardware issue with the communication port.

1

10 Volts low

The control card voltage from terminal 50 has dropped below 10 V. This is typically caused by an overloaded 10 V supply (exceeding 15 mA or below 590 Ω minimum resistance) or a short circuit in a connected potentiometer or its wiring. If left unresolved, this can lead to unstable control card operation or system shutdown.

2

Live zero error

This warning or alarm appears if programmed in 6-01 Live Zero Timeout Function. It indicates that the signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. Common causes include broken wiring or a faulty device sending the signal, which can lead to incorrect process control.

3

No motor connected

No motor is detected connected to the output of the frequency converter. This prevents the drive from starting or operating correctly, as it expects a motor load. Attempting to run without a motor can cause issues with the drive's output stage.

4

Mains phase loss

A phase is missing on the supply side, or the mains voltage imbalance is excessively high. This message can also indicate a fault within the input rectifier on the frequency converter. Unresolved mains phase loss can lead to severe damage to the frequency converter or connected motor.

5

DC link voltage high

The intermediate circuit voltage (DC) has risen above the high-voltage warning limit, which is dependent on the frequency converter's voltage rating. The unit is still active, but operating at an elevated voltage could stress internal components or lead to a trip if limits are exceeded.

6

DC link voltage low

The intermediate circuit voltage (DC) has dropped below the low-voltage warning limit, which is dependent on the frequency converter's voltage rating. The unit is still active, but operating with insufficient voltage could affect performance or lead to a trip.

7

DC overvoltage

If the intermediate circuit voltage exceeds its critical limit, the frequency converter will trip after a time delay. This fault often occurs due to regenerative braking, sudden load changes, or issues with the mains supply. Repeated overvoltage trips can damage the drive's power components.

8

DC under voltage

If the intermediate circuit voltage (DC link) drops below the under-voltage limit, the frequency converter checks for a 24 V DC back-up supply. If no back-up is connected, the unit trips after a fixed delay. This condition can lead to unexpected shutdowns and loss of motor control.

9

Inverter overload

The frequency converter is operating with an excessively high current for too long, nearing its thermal protection limit. The electronic thermal inverter protection counter issues a warning at 98% and an alarm trip at 100%. The unit cannot be reset until the counter drops below 90%, indicating a significant risk of damage to the inverter if prolonged.

10

Motor overload temperature

According to the electronic thermal protection (ETR), the motor is too hot. This fault occurs when the motor runs with more than 100% overload for an extended period. Unresolved motor overheating risks severe motor damage or premature failure.

11

Motor thermistor overtemperature

The motor's thermistor temperature sensor or its connection is faulty or disconnected. This means the drive cannot accurately monitor the motor's temperature, risking undetected overheating. An unresolved thermistor fault could lead to severe motor damage due to thermal stress if the motor is indeed overheating.

12

Torque limit

The motor torque has exceeded the programmed limits in parameter 4-16 (Motor Mode) or 4-17 (Generator Mode). This can be caused by excessive load, rapid acceleration/deceleration, or incorrect limit settings. Persistent torque limiting can hinder application performance or cause unexpected stops.

13

Over current

The inverter peak current limit (approximately 200% of the rated current) has been exceeded, causing the frequency converter to trip after about 1.5 seconds. This is often caused by shock loading, rapid acceleration with high inertia loads, or can occur after kinetic back-up. Repeated overcurrent can lead to damage to the inverter's power stage.

14

Earth (ground) fault

There is an undesirable current path from one or more output phases to earth, either in the cable connecting the frequency converter to the motor or within the motor itself. This fault indicates a serious insulation breakdown, posing a safety risk and potential for severe equipment damage if power is not immediately removed.

15

Hardware mismatch

A fitted option card or module is not compatible or operational with the current control board hardware or software version in the frequency converter. This prevents the unit from functioning correctly and requires contacting support for resolution. Incorrect component pairings can lead to system instability.

16

Short circuit

A direct short circuit condition has been detected either within the motor's windings or across its terminal connections. This is a highly critical fault that triggers a trip-lock, requiring a power cycle to reset after the cause is rectified. Operating with a short circuit can cause immediate and irreparable damage to the frequency converter's IGBTs or other power components.

17

Control Word Timeout

The drive has not received a valid control word from the external controller (e.g., PLC via fieldbus) within the expected timeframe. This indicates a communication failure, causing the drive to stop or trip for safety reasons.

18

Start Failed

The drive attempted to start the motor but failed to achieve successful operation. This could be due to mechanical issues, incorrect motor parameters, insufficient power, or an inability to overcome the initial load.

22

Hoist mechanical brake

This warning/alarm signals a problem with the hoist mechanical brake control. It can be triggered if the required torque reference is not achieved before the timeout specified in parameter 2-27 Torque Ramp Up Time expires, or if the expected brake feedback is not received within the time limits set by parameter 2-23 Activate Brake Delay and parameter 2-25 Brake Release Time. This prevents proper control of the mechanical brake, which is critical for hoisting applications.

23

Internal fan fault

This warning indicates that the frequency converter's internal fan is either not running or not properly detected, as monitored by an internal protective function. This can lead to insufficient cooling of the drive's internal components, risking overheating and potential damage. The fan monitor can be disabled via parameter 14-53 (Fan Monitor) if necessary for specific testing, but typically should remain active for protection.

24

External fan fault

This warning signifies that an external fan, monitored by the frequency converter's protective function, is not running or is not correctly mounted/detected. This indicates a potential cooling issue for external components or within the enclosure where the drive is installed, potentially leading to elevated operating temperatures. Similar to the internal fan, this monitor can be disabled via parameter 14-53 (Fan Monitor).

25

Brake Resistor Short-Circuited

The connected braking resistor has been detected as short-circuited. This prevents proper energy dissipation during braking, potentially damaging the drive's braking chopper or causing overvoltage trips during deceleration.

26

Brake resistor power limit

This warning/alarm indicates that the average power dissipated by the brake resistor over the last 120 seconds has exceeded 90% of its rated capacity. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-16 (AC brake Max. Current). If parameter 2-13 (Brake Power Monitoring) is configured for [2] Trip, the drive will fault and stop when the dissipation reaches 100%, signifying continuous excessive braking and potential overheating of the resistor.

27

Brake chopper fault

This warning/alarm indicates a short circuit in the brake IGBT, which disables the brake function. A critical consequence is that substantial power is continuously transmitted to the brake resistor, even if the brake function is inactive, creating a high voltage hazard and risking severe overheating of the resistor. This fault can also be triggered by an overheated brake resistor (using Klixon inputs 104 and 106) or in 12-pulse frequency converters if a disconnect or circuit breaker is opened while the unit is operating.

28

Brake Check Fault

An issue was detected during the drive's internal mechanical brake check routine. This can indicate a problem with the mechanical brake itself, its control circuitry, or the drive's monitoring, potentially leading to unsafe operation or motor movement when stopped.

29

Heat Sink overtemperature

The heat sink temperature has exceeded its maximum allowable limit, indicating an internal overheating condition within the frequency converter. This poses a significant risk of damage to the drive's power components if not addressed. The exact trip and reset temperatures are specific to the drive's power size, and the fault will automatically reset once the temperature drops below a predefined safe level.

30

Motor phase U missing

Motor phase U is not detected between the frequency converter and the motor. This indicates a break in the motor wiring for phase U or a problem with the motor's winding. Operating with a missing phase can cause motor damage, instability, and inefficient operation, potentially damaging the frequency converter output stage due to imbalanced loading.

31

Motor phase V missing

Motor phase V is not detected between the frequency converter and the motor. This indicates a break in the motor wiring for phase V or a problem with the motor's winding. Operating with a missing phase can cause motor damage, instability, and inefficient operation, potentially damaging the frequency converter output stage due to imbalanced loading.

32

Motor phase W missing

Motor phase W is not detected between the frequency converter and the motor. This indicates a break in the motor wiring for phase W or a problem with the motor's winding. Operating with a missing phase can cause motor damage, instability, and inefficient operation, potentially damaging the frequency converter output stage due to imbalanced loading.

33

Inrush fault

Too many power-ups have occurred within a short time period, leading to excessive inrush current events. This frequent power cycling prevents the unit from dissipating heat and can stress internal components, potentially shortening the drive's lifespan.

34

Fieldbus communication fault

The fieldbus communication option card is not functioning or communicating correctly. This prevents the drive from receiving commands or sending status information to the connected control system, leading to loss of remote control and monitoring capabilities. Unresolved, this fault will halt automated operation.

35

Option fault

An alarm specific to an option card has been received, likely due to a power-up issue or a communication fault with the installed option card. This indicates the option card is not functioning correctly, compromising any features or connectivity it provides. This may require further diagnosis depending on the specific option.

36

Mains failure

The frequency converter has detected a loss of incoming supply voltage, and the 'Mains Failure' parameter (14-10) is configured to generate an alarm. This indicates a power supply interruption to the drive, which will cause the motor to stop. Until mains power is restored, the drive cannot operate.

37

Phase imbalance

There is a significant current imbalance detected between the power units within the frequency converter. This can indicate issues with the motor, motor cabling, or an internal problem within the drive's power stage. Sustained phase imbalance can cause overheating in the motor or drive components and lead to premature failure.

38

Internal fault (General)

A general internal fault has been detected within the frequency converter, preventing normal operation. A specific sub-code, referenced in Table 7.6, provides more detailed diagnostic information about the nature of the internal issue. This fault indicates a critical hardware or software problem requiring specific troubleshooting based on the sub-code.

38.0

Internal Fault: Serial port initialization error

The internal serial communication port failed to initialize upon power-up or during operation. This can prevent communication with the LCP or external serial devices, indicating a possible internal hardware or firmware issue with the control board.

38.256-258

Internal Fault: Power EEPROM data error

The Electrically Erasable Programmable Read-Only Memory (EEPROM) on the power card, which stores crucial operational data, is either corrupted or obsolete. This hardware fault on the power card prevents the drive from properly initializing or operating.

38.512-519

Internal Fault: System error (512-519)

A general internal system error has occurred within a specific range, indicating a deeper hardware or firmware issue not covered by more specific sub-codes. This type of fault typically points to a critical internal component failure that prevents normal drive operation.

38.783

Internal Fault: Parameter value out of limits

An internal parameter's stored value has fallen outside its predefined minimum or maximum allowable range. This can be caused by data corruption, an incorrect parameter write, or a software anomaly, leading to unexpected drive behavior or shutdown.

38.1024-1284

Internal Fault: System error (1024-1284)

A general internal system error has occurred within a specific range, indicating a deeper hardware or firmware issue not covered by more specific sub-codes. This type of fault typically points to a critical internal component failure that prevents normal drive operation.

38.1299

Internal Fault: Option software in slot A too old

The software version on the option card installed in slot A is detected as being outdated or incompatible with the frequency converter's current firmware. This mismatch can lead to communication errors, incorrect functionality, or complete failure of the option card.

38.1300

Internal Fault: Option software in slot B too old

The software version on the option card installed in slot B is detected as being outdated or incompatible with the frequency converter's current firmware. This mismatch can lead to communication errors, incorrect functionality, or complete failure of the option card.

38.1315

Internal Fault: Option software in slot A not supported

The software on the option card installed in slot A is not recognized or supported by the frequency converter's firmware. This indicates a fundamental incompatibility, preventing the option card from integrating correctly with the drive's control system.

38.1316

Internal Fault: Option software in slot B not supported

The software on the option card installed in slot B is not recognized or supported by the frequency converter's firmware. This indicates a fundamental incompatibility, preventing the option card from integrating correctly with the drive's control system.

38.1379-2819

Internal Fault: System error (1379-2819)

A general internal system error has occurred within a specific range, indicating a deeper hardware or firmware issue not covered by more specific sub-codes. This type of fault typically points to a critical internal component failure that prevents normal drive operation.

38.2561

Internal Fault: Control card replacement required

The frequency converter's control card has been detected as faulty and is no longer able to perform its critical functions. This component is essential for all drive operations, and its failure will completely disable the drive.

38.2820

Internal Fault: LCP stack overflow

An internal memory stack overflow has occurred within the Local Control Panel (LCP) processor. This typically indicates a transient software issue or excessive processing demand within the LCP firmware, potentially leading to unresponsive controls or system crashes.

38.2821

Internal Fault: Serial port overflow

The internal serial communication buffer has overflowed, meaning data is being received faster than the drive can process it. This leads to data loss and unreliable serial communication, affecting remote control and monitoring via the serial port.

38.2822

Internal Fault: USB port overflow

The internal USB communication buffer has overflowed, indicating that data is being received faster than the drive can process it. This leads to data loss and unreliable USB communication, affecting diagnostics or parameter transfers.

38.3072-5122

Internal Fault: Parameter value out of limits (3072-5122)

An internal parameter's stored value has fallen outside its predefined minimum or maximum allowable range within a specific memory region. This can be caused by data corruption, an incorrect parameter write, or a software anomaly, leading to unexpected drive behavior or shutdown.

38.5123

Internal Fault: Option in slot A hardware incompatible

The hardware of the option card installed in slot A is fundamentally incompatible with the drive's control board hardware. This hardware mismatch prevents the option card from functioning correctly and may lead to system instability or other operational faults.

38.5124

Internal Fault: Option in slot B hardware incompatible

The hardware of the option card installed in slot B is fundamentally incompatible with the drive's control board hardware. This hardware mismatch prevents the option card from functioning correctly and may lead to system instability or other operational faults.

38.5376-6231

Internal Fault: System error (5376-6231)

A general internal system error has occurred within a specific range, indicating a deeper hardware or firmware issue not covered by more specific sub-codes. This type of fault typically points to a critical internal component failure that prevents normal drive operation.

39

Heatsink sensor fault

The frequency converter is not receiving a temperature signal from the heatsink sensor, specifically the IGBT thermal sensor on the power card. This loss of feedback means the drive cannot monitor critical internal temperatures, posing a significant risk of overheating and damage to the power semiconductors if not resolved.

45

Earth fault 2 (Ground fault)

A ground fault has been detected in the system, meaning current is flowing to earth through an unintended path. This is a critical safety issue that can cause electrical shock, equipment damage, or fire if not immediately addressed.

46

Power card supply out of range

One or more of the internal power supplies (24V, 5V, ±18V) generated by the switch-mode power supply (SMPS) on the power card are operating outside their acceptable voltage range. This indicates an issue with the power card's internal power regulation, which can affect the functionality of other components and lead to instability or failure.

47

24V supply low

The 24V DC supply generated by the switch-mode power supply (SMPS) on the power card is operating below its acceptable voltage range. This low voltage can cause erratic behavior or non-operation of components that rely on the 24V supply, potentially leading to incorrect sensor readings or control issues.

48

1.8V supply low

The 1.8V DC supply on the control card, crucial for its internal logic, has dropped below its allowable limits. This low voltage indicates a potential fault on the control card itself or an overload caused by an option card, leading to unstable operation or complete control card failure.

49

Speed limit

The motor speed is not within the specified range set in parameters 4-11 (Motor Speed Low Limit) and 4-13 (Motor Speed High Limit), generating a warning. If the speed drops below the limit set in 1-86 (Trip Speed Low) (except during start/stop), the frequency converter will trip. This indicates an operational deviation that could affect process control or product quality.

50

AMA calibration failed

The Automatic Motor Adaptation (AMA) calibration process has failed. This means the drive could not successfully characterize the connected motor, which is critical for optimal performance and protection. Without successful AMA, motor control may be suboptimal or protection features less effective, impacting efficiency.

51

AMA check U nom and I nom

The settings for motor voltage, motor current, or motor power are incorrect, preventing successful Automatic Motor Adaptation (AMA). Incorrect motor data can lead to poor motor control, reduced efficiency, and inadequate motor protection. This also impacts the drive's ability to properly characterize the motor.

52

AMA low I nom

The motor current is detected as too low for the Automatic Motor Adaptation (AMA) process to properly function. This may indicate an incorrect motor data entry or an undersized motor for the drive's capabilities. Incorrect current settings hinder accurate motor characterization and optimal drive performance.

53

AMA: Motor too big

The connected motor is too large for the Automatic Motor Adaptation (AMA) function to operate successfully with the current drive sizing or parameter limits. This means the drive cannot accurately identify the motor's characteristics, leading to an inability to optimize control.

54

AMA: Motor too small

The connected motor is too small for the Automatic Motor Adaptation (AMA) function to operate successfully. This mismatch in sizing or parameter limits means the drive cannot accurately identify the motor's characteristics, leading to an inability to optimize control.

55

AMA: Parameter out of range

The Automatic Motor Adaptation (AMA) cannot run because one or more parameter values related to the motor are outside of the acceptable range for the AMA algorithm. This indicates an invalid motor configuration that prevents the drive from accurately modeling the motor.

56

AMA interrupted by user

The Automatic Motor Adaptation (AMA) routine was manually interrupted before completion. This means the drive did not fully characterize the motor, and subsequent operation may not be optimized.

57

AMA internal fault (Persistent)

An internal fault occurred during the Automatic Motor Adaptation (AMA) process. While a single occurrence might be transient, repeated occurrences suggest a more persistent issue within the drive's control logic or its interaction with the motor, potentially heating the motor due to repeated attempts.

58

AMA internal fault (Contact supplier)

A persistent internal fault has occurred during the Automatic Motor Adaptation (AMA) process that cannot be resolved through simple restarts. This indicates a potentially deeper issue with the drive's internal diagnostics or hardware.

59

Current limit exceeded

The motor current has exceeded the value set in parameter 4-18 (Current Limit). This indicates that the motor is drawing excessive current, potentially due to overload, incorrect motor data, or a mechanical issue, which could lead to motor or drive overheating and damage if not addressed.

60

External interlock

A digital input signal has indicated an external fault condition, causing the frequency converter to trip. This means an external safety or control system has commanded the drive to stop due to a detected issue. The external fault must be cleared before normal operation can resume.

61

Feedback error

An inconsistency has occurred between the calculated motor speed and the speed measurement received from the feedback device (e.g., encoder). This indicates a potential issue with the feedback device, its wiring, or the drive's speed calculation, which can lead to unstable speed control or unexpected motor behavior.

62

Output frequency at maximum limit

The frequency converter's output frequency has reached or exceeded the maximum value set in parameter 4-19 (Max Output Frequency). This typically occurs when the drive is commanded to run faster than its configured limit, potentially indicating an over-speed condition or an incorrectly set limit for the application.

63

Mechanical brake low

The actual motor current failed to exceed the configured release brake current within the specified start delay time window. This indicates an issue with the mechanical brake's release mechanism, potentially due to a stuck brake, insufficient current to release it, or incorrect timing settings, preventing the motor from starting.

64

Voltage Limit (DC-link voltage insufficient)

The combination of the current load and motor speed demands a motor voltage higher than the actual DC-link voltage available in the frequency converter. This indicates that the drive cannot supply the necessary voltage for the commanded operation, potentially due to a low DC-link, excessive load, or too high a speed command for the input voltage.

65

Control card over temperature

The control card temperature has reached its cut-out limit of 80 °C, indicating excessive heat within the control section of the frequency converter. This can lead to erratic behavior, reduced lifespan, or permanent damage to the control card if not addressed. Proper cooling is essential for its reliability.

66

Heatsink temperature low

The frequency converter's heatsink temperature, measured by a sensor in the IGBT module, is too low for safe operation. This indicates the unit is too cold to operate efficiently or without condensation risk. Operation at extremely low temperatures can affect component reliability and performance.

67

Option module configuration has changed

One or more option modules (e.g., fieldbus cards, I/O extensions) have either been added or removed since the last power-down cycle. The drive detects a change in its hardware configuration and requires user confirmation. This alarm serves as a notification and requires a reset to ensure the change was intentional before proceeding.

68

Safe Stop activated

The Safe Stop function has been activated, bringing the motor to a controlled stop and preventing unintended restart. This is a critical safety feature typically triggered by an external safety input. The drive will remain in this state until the safety input is cleared and a reset commanded.

69

Power card temperature

The temperature sensor on the power card indicates that it is either too hot or too cold, exceeding safe operating limits. Extreme temperatures can severely affect the power components (IGBTs, capacitors), leading to reduced lifespan, performance issues, or immediate failure of the drive if not corrected.

70

Illegal FC configuration

The installed control card and power card within the frequency converter are incompatible with each other. This indicates an incorrect pairing of components, potentially due to wrong spare parts or an assembly error. The drive cannot operate with this configuration and requires corrective action.

80

Drive initialised to default value

The frequency converter's parameter settings have been reset to their factory default values, typically after a manual reset action. This alarm serves as a notification that custom configuration has been lost. The drive will operate with default parameters until reconfigured, potentially affecting application performance and safety.

92

No flow

A no-flow condition has been detected in the system, and parameter 22-23 (No-Flow Function) is set to trigger an alarm. This indicates a critical deviation in the process, such as a pump running dry or a blocked pipe. Continued operation in a no-flow state can damage pumps or other system components.

250

New Spare Part

This alarm indicates that a major power-related component, specifically the power section or switch mode power supply, within the frequency converter has been replaced. It serves as a service notification rather than an operational fault, confirming a hardware change. The drive should function normally after this alarm, assuming proper installation of the new part.

251

New Type Code

The frequency converter has detected a change in its internal type code, typically occurring after a control card replacement or a full drive swap. This alarm acts as an informational message signaling a significant change in the drive's identity or configuration. While not an immediate operational fault, it indicates a need to verify parameter settings for the new hardware.

256

Internal fault (Power EEPROM data defective or too old)

The power EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing power section parameters.

257

Internal fault (Power EEPROM data defective or too old)

The power EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing power section parameters.

258

Internal fault (Power EEPROM data defective or too old)

The power EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing power section parameters.

512

Internal fault (Control board EEPROM data defective or too old)

The control board EEPROM data is defective or too old. This indicates a corruption or obsolescence of the non-volatile memory storing control board parameters.

513

Internal fault (Communication timeout reading EEPROM data)

A communication timeout occurred while attempting to read EEPROM data. This suggests an issue with data access from the non-volatile memory.

514

Internal fault (Communication timeout reading EEPROM data)

A communication timeout occurred while attempting to read EEPROM data. This suggests an issue with data access from the non-volatile memory.

515

Internal fault (Application-oriented control cannot recognize EEPROM data)

The application-oriented control system cannot recognize the EEPROM data. This indicates an incompatibility or corruption in the stored application parameters.

ALARM 2

Live zero error

The signal on one of the analog inputs is less than 50% of the programmed minimum value. This condition, appearing if parameter 6-01 Live Zero Timeout Function is programmed, often indicates broken wiring or a faulty sensor/device sending the analog signal, risking incorrect operation or control.

ALARM 3

No motor

No motor is connected to the output of the frequency converter. This prevents motor operation and could indicate a wiring issue or incorrect system setup.

ALARM 4

Mains phase loss

A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options for handling this are programmed in parameter 14-12 Function at Mains Imbalance. Operating with a missing phase can severely damage the motor or the frequency converter.

ALARM 7

DC overvoltage

The DC-link voltage has exceeded its limit, causing the frequency converter to trip after a certain time. This often occurs due to regenerative braking or excessive mains voltage, which can damage the inverter section if not mitigated.

ALARM 8

DC under voltage

The DC-link voltage has dropped below the undervoltage limit. If no 24V DC back-up supply is connected, the frequency converter will trip after a fixed time delay (varying by unit size). This indicates insufficient input power, which can lead to uncontrolled motor shutdown.

ALARM 9

Inverter overload

The frequency converter has been operating with more than 100% overload for too long, triggering a warning at 98% and an alarm at 100%. The unit will trip, and cannot be reset until the internal thermal counter falls below 90%. Prolonged overload can severely damage the inverter's power components.

ALARM 10

Motor overload temperature

The motor's electronic thermal protection (ETR) indicates it is too hot. This fault occurs when the motor runs with more than 100% overload for an extended period, risking damage to motor windings and insulation. The frequency converter issues a warning at >90% and trips at 100% (depending on parameter 1-90 Motor Thermal Protection settings).

ALARM 11

Motor thermistor overtemp

The motor thermistor indicates an overtemperature condition, or it may be disconnected. The frequency converter can be configured to issue either a warning or an alarm based on parameter 1-90 Motor Thermal Protection. This fault protects the motor from thermal damage.

ALARM 12

Torque limit

The motor's torque has exceeded the value set in parameter 4-16 Torque Limit Motor Mode or the generator torque limit in parameter 4-17 Torque Limit Generator Mode. This condition can be a warning or escalate to an alarm and trip, protecting the mechanical system from excessive stress.

ALARM 13

Over current

The inverter peak current limit (approximately 200% of rated current) has been exceeded. The warning lasts about 1.5 seconds before the frequency converter trips and issues an alarm. This is often caused by shock loading, rapid acceleration of high-inertia loads, or can occur after kinetic back-up. An overcurrent condition can rapidly damage the inverter's power components.

ALARM 14

Earth (ground) fault

Current is flowing from the output phases to ground, either in the cable between the frequency converter and the motor, or within the motor itself. This is a severe fault that can cause electrocution, fire, and damage to the frequency converter or motor.

ALARM 15

Hardware mismatch

A fitted option card is not operational with the current control board hardware or software version. This indicates an incompatibility preventing proper functioning of the option.

ALARM 16

Short circuit

There is a short circuit condition present in the motor or its wiring. This is a critical fault that can lead to immediate damage of the frequency converter's output stage if not quickly resolved.

ALARM 30

Motor phase U missing

The motor phase U connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.

ALARM 31

Motor phase V missing

The motor phase V connection between the frequency converter and the motor is missing or interrupted. This prevents proper motor operation and can lead to damage if ignored.

ALARM 32

Motor phase W missing

Motor phase W between the frequency converter and the motor is missing. This indicates a loss of one of the three phases supplying the motor, which can lead to motor damage or failure if operated in this state.

ALARM 33

Inrush fault

Too many power-ups have occurred within a short time period. This can stress components due to repeated inrush currents, potentially causing premature failure of the frequency converter.

ALARM 34

Fieldbus communication fault

The fieldbus on the communication option card is not working. This prevents remote control or monitoring of the frequency converter, potentially leading to a loss of process control.

ALARM 36

Mains failure

The supply voltage to the frequency converter is lost. This warning/alarm is active only if parameter 14-10 Mains Failure is not set to [0] No Function. This causes a complete loss of power to the drive and connected motor.

ALARM 38

Internal fault

An unspecified internal fault has occurred within the frequency converter. This indicates a potential hardware or firmware issue requiring specialized attention, and continued operation may cause further damage.

ALARM 44

Earth fault II

There is an electrical discharge from one of the output phases to ground, either in the cable between the frequency converter and the motor or within the motor itself. This poses a significant safety risk and can cause severe equipment damage.

ALARM 46

Gate drive voltage low

The supply voltage on the power card, which generates 24 V, 5 V, and ±18 V, is out of range. This indicates a problem with the switch mode power supply (SMPS) on the power card, affecting the drive's ability to control the motor's power transistors.

ALARM 47

24 V supply low

The detected 24 V DC voltage on terminal 12 of the control card has dropped below 18 V. This can impact the reliability of the control card and any external devices powered by this supply, potentially leading to incorrect operation or shutdowns.

ALARM 51

AMA check Unom and Inom

The settings for motor voltage, motor current, or motor power are presumably incorrect. This prevents the Automatic Motor Adaptation (AMA) function from accurately identifying motor parameters, leading to suboptimal or incorrect motor control.

ALARM 52

AMA low Inom

The motor current detected during the Automatic Motor Adaptation (AMA) process is too low. This usually indicates an incorrect motor current setting in the parameters or an issue with the motor connection itself, hindering proper parameter identification.

ALARM 53

AMA motor too big

The motor connected is too large for the Automatic Motor Adaptation (AMA) function to be successfully performed by this frequency converter. The drive may not be adequately sized for the motor, which can lead to inaccurate parameter identification or drive overload.

ALARM 54

AMA motor too small

The motor connected is too small for the Automatic Motor Adaptation (AMA) function to be successfully performed. This can lead to inaccurate motor parameter identification, potentially causing suboptimal motor control or unexpected behavior.

ALARM 55

AMA Parameter out of range

The parameter values found from the motor during the Automatic Motor Adaptation (AMA) process are outside the acceptable range for the frequency converter. This indicates an incompatibility between the motor and drive or severely incorrect initial motor data settings.

ALARM 56

AMA interrupted by user

The Automatic Motor Adaptation (AMA) process was interrupted by the user. This is not an error but an indication that the parameter identification sequence was not completed, meaning the drive may not be optimally tuned for the motor.

ALARM 57

AMA timeout

The Automatic Motor Adaptation (AMA) process failed to complete within the expected time frame. This can occur due to various reasons, including excessive motor heating from repeated attempts, which can affect resistance measurements and prolong the process.

ALARM 58

AMA internal fault

An internal fault occurred within the frequency converter during the Automatic Motor Adaptation (AMA) process. This suggests a problem with the drive's internal diagnostics or control logic, preventing accurate motor parameter identification.

ALARM 60

External interlock

An external interlock signal has been activated, causing the frequency converter to trip. This typically originates from a safety device or process control, indicating a condition that requires intervention before normal operation can resume to prevent injury or damage.

ALARM 69

Power card temperature

The temperature on the frequency converter's power card is outside its acceptable operating range (either too high or too low). Extreme temperatures can lead to premature component failure or immediate drive shutdown to prevent damage.

ALARM 70

Illegal power section configuration

The control card and power card installed in the frequency converter are incompatible with each other. This prevents the drive from starting or operating correctly, requiring compatible hardware components for functionality.

ALARM 80

Drive initialised to default value

The frequency converter's parameter settings have been reset to their factory default values, typically following a manual reset operation. This means all previous application-specific configurations are lost, and the drive will operate with generic settings.

ALARM 126

Motor Rotating

A high back EMF voltage has been detected, indicating that the Permanent Magnet (PM) motor is rotating while the drive is attempting to control or start it. This can interfere with the drive's control algorithms and prevent a successful start.

WARNING 1

10 Volts low

The control card's 10 V supply from terminal 50 is less than 10 V, indicating it is overloaded. This can affect connected sensors or potentiometers, leading to incorrect control signals or loss of functionality.

WARNING 5

DC link voltage high

The DC-link voltage is higher than the warning limit, which depends on the frequency converter's voltage rating. The unit remains active but operating at an elevated DC link voltage can shorten component life or lead to an overvoltage trip.

WARNING 6

DC link voltage low

The DC-link voltage is lower than the warning limit, which depends on the frequency converter's voltage rating. The unit remains active but operating at a reduced DC link voltage can affect motor performance or lead to an undervoltage trip.

WARNING 59

Current limit

The motor current has exceeded the value set in parameter 4-18 (Current Limit). The drive is actively limiting the current to protect itself and the motor, but prolonged operation at this limit indicates an overloaded condition that can cause wear or damage.

WARNING 127

Back EMF too high

This warning, specific to PM motors, indicates that the back electromotive force (EMF) voltage has exceeded 90% of the inverter's maximum voltage threshold (U invmax) and has remained high for over 5 seconds. This condition suggests that the motor is generating excessive voltage, potentially due to overspeeding or regenerative braking issues, which could lead to overvoltage trips.

WARNING 200

Fire Mode

The frequency converter has been activated into 'Fire Mode'. This mode forces the drive to continue operation even under fault conditions to maintain critical systems (e.g., smoke extraction fans) during an emergency. Be aware that this overrides normal safety shutdowns.

WARNING 202

Fire Mode Limits Exceeded

While in Fire Mode, one or more warranty-voiding alarms have been suppressed, indicating that the drive is operating under extreme conditions beyond its normal limits. This significantly increases the risk of equipment damage and voids the product warranty.

WARNING/ALARM 2

Live zero error

The signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. This condition is typically caused by broken wiring, a loose connection, or a faulty signal-sending device connected to the frequency converter's analog input.

WARNING/ALARM 3

No motor

No motor is detected as connected to the output of the frequency converter. This condition prevents the drive from operating and indicates a potential wiring issue or a missing motor connection.

WARNING/ALARM 4

Mains phase loss

A phase is missing on the supply side of the frequency converter, or the mains voltage imbalance is excessively high. This message can also appear due to a fault in the input rectifier within the frequency converter, potentially leading to drive malfunction or damage.

WARNING/ALARM 7

DC overvoltage

The DC-link voltage inside the frequency converter has exceeded its predefined limit. This often occurs during deceleration of high inertia loads, where regenerative energy is fed back into the DC link, and can lead to component damage or drive trips if not controlled.

WARNING/ALARM 8

DC under voltage

The DC-link voltage has dropped below the undervoltage limit. This typically indicates an insufficient or fluctuating supply voltage to the frequency converter, leading to a drive trip after a fixed time delay, which varies by unit size. Continued operation with low voltage can cause instability.

WARNING/ALARM 9

Inverter overloaded

The frequency converter is experiencing an overload, with the internal thermal counter indicating that current levels are exceeding 100% for an extended duration. This activates electronic thermal protection, issuing a warning at 90% and an alarm trip at 100% to prevent damage. The drive cannot be reset until the counter falls below 90%.

WARNING/ALARM 95

Broken belt

The torque measured by the motor is below the threshold set for no-load conditions, strongly indicating a broken or severely slipping belt in the mechanical system. This results in a loss of power transmission to the driven equipment.